Step
|
Action
|
---|---|
1
|
Access the calibration adjustment screen
|
2
|
Double click on channel 0.
Result: A question appears ‘Do you wish to switch to recalibration mode?’.
|
3
|
Reply to this question with Yes.
Result: The calibration window appears.
|
4
|
Connect a reference voltage on the voltage input of channel 0, according to the range to be calibrated:
Caution: the reference 5 V is used to recalibrate the whole measurement channel for ranges 0..20 mA and 4..20 mA, with the exception of the 250 Ohm current shunt situated on the current entry.
|
5
|
Once the reference has been connected to the voltage input (e.g. 10 V), use the Reference drop-down list box to select this value. Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the OK command button. The ranges linked to this reference (e.g. +/-10 V and 0..10 V) are then calibrated automatically.
|
6
|
Calibrate the module for other ranges, if applicable.
the Return to Factory Parameters command button cancels all previous calibrations, and return to the original calibration settings configured in the factory.
|
7
|
Press the Save command button, in order to recognize and save the new calibration in the module. If you exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost ..
|