LOOSE WIRING CAUSES ELECTRIC SHOCK
Do not insert more than one wire per connector of the terminal block without a twin cable end.
Failure to follow these instructions will result in death or serious injury.
|
![]() ![]() |
FIRE HAZARD
Use only the recommended wire sizes.
Failure to follow these instructions will result in death or serious injury.
|
Cable type
|
![]() 1 solid conductor
|
![]() 1 stranded cable(1)
|
![]() 1 stranded cable with single cable end
![]() |
![]() 2 solid conductors, only with twin cable end
![]() |
![]() 2 solid conductors, only with twin cable end
![]() |
AWG
|
24...12
|
22...14
|
22...14
|
2x24...2x16
|
2x22...2x16
|
mm2
|
0,205…3,310
|
0,357…2,285(2)
|
0,324…2,285(2)
|
2x0,205…2x0,82
|
2x0,324…2x1,44(2)
|
AWG
|
24...12
|
22...14
|
22...14
|
2x24...2x16
|
2x22...2x16
|
(1) Minimum individual wire size in stranded cable without cable end is AWG 30 (0,0507 mm2). (2) Depending on stranding. |
![]() |
UNINTENDED EQUIPMENT OPERATION
Do not power sensors connected to the modules of one rack with the power supply of another rack.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Power supply module
|
Copper wire size
|
|
---|---|---|
2.5 mm2 (12 AWG)
|
1.5 mm2 (14 AWG)
|
|
BMXCPS2010
|
30 m (98.4 ft)
|
20 m (65.6 ft)
|
BMXCPS3020(H)
BMXCPS4022(H)
|
15 m (49.2 ft)
|
10 m (32.8 ft)
|