Power Supply Reference
|
Maximum available power:
|
||
---|---|---|---|
3V3_BAC
|
24V_BAC
|
24V_SENSORS
|
|
BMXCPS2000
(100...240 Vac)
|
8.3 W (2.5 A)
|
16.5 W (0.7 A)
|
10.8 W (0.45 A)
|
3V3_BAC and 24V_BAC cumulated = 16.5 W
|
|||
3V3_BAC, 24V_BAC, and 24V_SENSORS cumulated = 20 W
|
|||
BMXCPS2010
(24 Vdc)
|
8.3 W (2.5 A)
|
16.5 W (0.7 A)
|
–
|
3V3_BAC and 24V_BAC cumulated = 16.5 W
|
|||
BMXCPS3020
(24...48 Vdc)
|
15 W (4.5 A)
|
31.2 W (1.3 A)
|
–
|
3V3_BAC and 24V_BAC cumulated = 31.2 W
|
|||
BMXCPS3020H(1)
(24...48 Vdc)
|
15 W (4.5 A)
11.25 W (3.375 A)
|
31.2 W (1.3 A)
23.4 W (0.975 A)
|
–
|
3V3_BAC and 24V_BAC cumulated = 31.2 W (23.4 W)
|
|||
BMXCPS3500
(100...240 Vac)
|
15 W (4.5 A)
|
31.2 W (1.3 A)
|
21.6 W (0.9 A)
|
3V3_BAC and 24V_BAC cumulated = 31.2 W
|
|||
3V3_BAC, 24V_BAC, and 24V_SENSORS cumulated = 36 W
|
|||
BMXCPS3500H(1)
(100...240 Vac)
|
15 W (4.5 A)
11.25 W (3.375 A)
|
31.2 W (1.3 A)
23.4 W (0.975 A)
|
21.6 W (0.9 A)
16.2 W (0.5 A)
|
3V3_BAC and 24V_BAC cumulated = 31.2 W (23.4 W)
|
|||
3V3_BAC, 24V_BAC, and 24V_SENSORS cumulated = 36 W (27 W)
|
|||
BMXCPS3540T(1)
(125 Vdc)
|
15 W (4.5 A)
11.25 W (3.375 A)
|
31.2 W (1.3 A)
23.4 W (0.975 A)
|
21.6 W (0.9 A)
16.2 W (0.5 A)
|
3V3_BAC and 24V_BAC cumulated = 31.2 W (23.4 W)
|
|||
3V3_BAC, 24V_BAC, and 24V_SENSORS cumulated = 36 W (27 W)
|
|||
BMXCPS4002H(2)
(100...240 Vac)
|
16.5 W (5 A)
|
40 W (1.67 A)
|
–
|
3V3_BAC and 24V_BAC cumulated = 40 W
|
|||
BMXCPS4022(H)(2)
(24...48 Vdc)
|
16.5 W (5 A)
|
40 W (1.67 A)
|
–
|
3V3_BAC and 24V_BAC cumulated = 40 W
|
|||
BMXCPS3522(H)(2)
(125 Vdc)
|
16.5 W (5 A)
|
40 W (1.67 A)
|
–
|
3V3_BAC and 24V_BAC cumulated = 40 W
|
|||
(1) For the power supply modules that can operate in an extended temperature range, the usable powers are subject to derating (written in bold) in the temperature range of 60...70 °C (140...158 °F). (2) There is no derating for the redundant power supply modules. |
![]() |
UNEXPECTED EQUIPMENT OPERATION
Do not exceed the 24V_SENSORS output power rating.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
![]() |
UNEXPECTED EQUIPMENT OPERATION
Do not exceed the total useful power rating of the module.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
NOTICE
|
RECOVERY TIME AFTER TRIPPING
After tripping, remove the power to the power supply module and wait 5 minutes before applying the power again.
Failure to follow these instructions can result in equipment damage.
|