Characteristics of the primary block
|
Nominal voltage
|
100...240 Vac
|
|
Voltage range
|
85...132 Vac
170...264 Vac
|
||
Nominal frequency/frequency range
|
50...60 Hz
/ 47...63 Hz
|
||
Power
|
130 VA
|
||
Nominal current consumption
|
1.1 A at 115 Vac
0.55 A at 230 Vac
|
||
Initial power-up at 25 °C(1)
|
InRush current I
|
≤ 30 A at 115 Vac
≤ 60 A at 230 Vac
|
|
I2t
at locking
|
≤ 1 A2s at 115 Vac
≤ 4 A2s at 230 Vac
|
||
It
at locking
|
≤ 0.1 As at 115 Vac
≤ 0.15 As at 230 Vac
|
||
Acceptable duration of power interruptions
|
≤ 10 ms
|
||
Built-in over-current protection
|
By internal, inaccessible fuse
|
||
Characteristics of the secondary block
|
Total useful power
|
40 W on 24V BAC only
|
|
3V3_BAC output
|
Nominal voltage
|
3.3 Vdc
|
|
Nominal current
|
5 A
|
||
Power (typical)
|
16.5 W
|
||
24V_BAC output
|
Nominal voltage
|
24 Vdc
|
|
Nominal current
|
1.67 A
|
||
Power (typical)
|
40 W
|
||
3V3_BAC and 24V_BAC output protection
|
Against overload, short circuits and over-voltage
|
||
Characteristics of the auxiliary functions
|
Alarm relay
|
Normally open dry contacts
|
|
Display
|
Front panel LED
|
||
Back-up battery
|
No
|
||
Isolation
|
Dielectric resistance
at 50 Hz-1mn
|
Primary/secondary (24V_BAC/3V3_BAC)
|
1,500 Vrms
|
Primary/ground
|
1,500 Vrms
|
||
Insulation resistance
|
Primary/secondary
|
≥ 100 MΩ
|
|
Primary/ground
|
≥ 100 MΩ
|
||
Operating temperature
|
BMXCPS4002
|
0...60 °C (32...140 °F)
|
|
BMXCPS4002H
|
-25...70 °C (-13...158 °F)
|
||
1These values are to be taken into account for the start-up of several devices simultaneously or for establishing the size of the protection devices. |