IO Connection Diagnostics Object
(Original Document)
Overview
The IO Connection Diagnostics object presents the instances, attributes and services described below.
Class ID
352 (hex), 850 (decimal)
Instance IDs
The IO Connection Diagnostics object presents two instance values:
Attributes
IO Connection Diagnostics object attributes are associated with each instance, as follows:
Instance ID = 0 (class attributes):
Attribute ID
Description
GET
SET
01
Revision
X
02
Max Instance
X
X = supported
— = not supported
Instance ID = 1 to 256 (instance attributes):
Attribute ID
Description
Type
GET
SET
Value
01
IO Communication Diagnostics
STRUCT
X
X
IO Production Counter
UDINT
Increments at each production
IO Consumption Counter
UDINT
Increments at each consumption
IO Production Send Errors Counter
UINT
Increments each time a production is not sent
IO Consumption Receive Errors Counter
UINT
Increments each time a consumption is received with a detected error
CIP Connection Timeout Errors
UINT
Increments when a connection times out
CIP Connection Opening Errors
UINT
Increments each time a connection is unable to open
CIP Connection State
UINT
State of the Connection Bit
CIP Last Error General Status
UINT
General status of the last error detected on the connection
CIP Last Error Extended Status
UINT
Extended status of the last error detected on the connection
Input Communication Status
UINT
Communication status of the inputs (see table, below)
Output Communication Status
UINT
Communication status of the outputs (see table, below)
02
Connection Diagnostics
STRUCT
X
X
Production Connection ID
UDINT
Connection ID for production
Consumption Connection ID
UDINT
Connection ID for consumption
Production RPI
UDINT
RPI for production
Production API
UDINT
API for production
Consumption RPI
UDINT
RPI for consumption
Consumption API
UDINT
API for consumption
Production Connection Parameters
UDINT
Connection parameters for production
Consumption Connection Parameters
UDINT
Connection parameters for consumption
Local IP
UDINT
Local UDP Port
UINT
Remote IP
UDINT
Remote UDP Port
UINT
Production Multicast IP
UDINT
Multicast IP used for production (or 0)
Consumption Multicast IP
UDINT
Multicast IP used for consumption (or 0)
Protocols Supported
UDINT
Protocol supported on the connection:
1 = EtherNet/IP
X = supported
— = not supported
The following values describe the structure of the instance attributes: CIP Connection State, Input Communication Status, and Output Communication Status:
Bit Number
Description
Values
15...3
Reserved
0
2
Idle
0 = no idle notification
1 = idle notification
1
Consumption inhibited
0 = consumption started
1 = no consumption
0
Production inhibited
0 = production started
1 = no production
Services
The EtherNet/IP Interface Diagnostics object performs the following services upon the listed object types:
Service ID
Description
Class
Instance
Notes
hex
dec
01
01
Get_Attributes_All
X
X
Returns the value of all attributes.
0E
14
Get_Attribute_Single
X
Returns the value of the specified attribute.
4C
76
Get_and_Clear
X
Returns and clears the values of all instance attributes.
X = supported