I/O Scanning Service
Original instructions
Introduction
The I/O Scanner is used to periodically:
The I/O Scanner is used to periodically read or write remote inputs and outputs on the Ethernet network without specific programming.
Configure the I/O Scanner with Control Expert.
NOTE: I/O scanning is not supported by the Ethernet port of BMX P34 20x0 CPUs.
Characteristics
This service comprises the following essential elements:
During operation, the module:
Recommended Use
Scanning is performed only when the PLC is in Run mode.
This service operates with all devices that support Modbus TCP/IP server mode.
The exchange mechanism, which is transparent to the user, is executed with these request types (as long as the remote devices support them):
I/O Scanner Operation
This figure illustrates the scanning of remote inputs and outputs:
1 
As soon as the PLC switches to Run mode, the module successfully opens a connection for each scanned device. (One connection is made for each line entered in the table of scanned devices.)
2 
Then the module periodically reads input words and reads/writes output words for each device.
3 
If the PLC switches to Stop mode, the connections to all devices are closed.
Summary of Functionality
The I/O scanning service:
Each I/O Scanner device can be enabled/disabled.
NOTE: These status bits show whether the module's input/output words have been refreshed.