The BMX NOC 0401 module displays the following indicators in the LED display area:
The module also displays the following LED indicators next to each Ethernet port connector:
Use the LED display to diagnose the state of the module, as follows:
LED
|
Color
|
Description
|
RUN
|
Green
|
|
ERR
|
Red
|
-
Off: The module is operating normally.
-
Blinking Red: The module is not configured (or the configuration is in progress), or backplane communication has stopped.
-
Steady Red: The module has detected an event.
|
MS (Module Status)
|
Green/ Red
|
-
Off: Power is not being supplied to the module.
-
Steady Green: The module is operating normally.
-
Blinking Green: The module has not been configured.
-
Steady Red: The module has detected a major event.
-
Blinking Red: The module has detected a recoverable event.
|
NS (Network Status)
|
Green/ Red
|
-
Off: Power is not being supplied to the module, or the module has not been assigned an IP address.
-
Steady Green: The module has established at least one CIP connection.
-
Blinking Green: The module has obtained an IP address but has not established any CIP connections.
-
Steady Red: The module has detected that its IP address is a duplicate IP address.
-
Blinking Red: One or more CIP connection (with the module as target) have timed out.
|
ETH STS (Ethernet Status)
|
Amber
|
-
Off: No power is supplied to the module.
-
Steady Amber: Indicates that the module is operating normally.
-
Four flashes: The module has detected a duplicate IP address.
-
Five flashes: The module is waiting for a served IP address.
-
Six flashes: The module is using its default IP address.
-
Seven flashes: The module has detected a configuration error.
NOTE: If more than one diagnostic condition exists simultaneously, the Ready LED displays the shortest flash sequence.
|
LNK (Link)
|
Yellow/ Green
|
-
Off: An Ethernet link has not been established.
-
Yellow: A 10 Mbit Ethernet link has been established
-
Green: A 100 Mbit Ethernet link has been established
|
ACT (Activity)
|
Green
|
|