Use the BMENUA0100 module.
web page to view dynamic data describing the operation of the OPC UA server embedded in theDiagnostic Data
web page displays the following read-only data. Note that all numeric values are in decimal format:
Field |
Description |
|
---|---|---|
PLC Diagnostic |
||
EPAC |
CPU IP address. |
|
Device Identity |
CPU part number. |
|
Device Version |
CPU firmware version. |
|
Device Status |
Connection status with CPU: Good, Bad, Uncertain, Unknown, Missing. |
|
Frame Time Out (in ms) |
The maximum length of time the OPC UA server will wait for an answer from a device after sending a request. For example, 1000. |
|
Maximum Channel number |
Number of connections opened by OPC UA server on the CPU. |
|
Channels used for non-Timestamping |
Number of connections that carry application data. |
|
Channels used for Timestamping |
||
Request Length |
Length of request for communication with CPU. |
|
Application Name (Device) |
Control Expert project name. |
|
Application Version (Device) |
Application checksum and signatures. |
|
Preload data dictionary |
Available or Unavailable for application in PAC. |
|
Timestamping Status |
Timestamping status is displayed:
|
|
List of devices with source time stamping configured |
If timestamping is enabled, a list of devices is displayed indicating for each device:
|
|
OPC UA Diagnostic |
||
Endpoint url (IPV4) |
OPC UA server IPv4 address, in the format: “opc.tcp://<IPv4 address>:<port number>”. For example: opc.tcp://192.168.2.142:4840 |
|
Fast Sampling Rate |
Indicates if the Fast sampling rate setting is selected:
|
|
Number of connected sessions |
Total number of client sessions supported by the BMENUA0100 embedded OPC UA server. |
|
Subscription(s) Information: |
Information describing the variables monitored by the OPC UA server that are included in one or more subscriptions. |
|
Number of monitored item(s) from internal Server node: |
||
Number of specific monitored item(s): |
||
Number of non specific monitored item(s): |
||
Number of TimeStamped monitored item(s) with monitoring mode not disabled: |
||
Total Number of monitored item(s): |
||
Current number of timers |
The number of configured sampling intervals for the BMENUA0100 embedded OPC UA server: |
|
Timer list |
A list describing each sampling interval (i.e., timer) monitored by the BMENUA0100 embedded OPC UA server. Each item indicates:
|