This table describes the status of the services that run in the primary and standby BMENOR2200H modules at the RUN and STOP PAC states:

Service List

Primary BMENOR2200H Module

Standby BMENOR2200H Module

PAC State

RUN

STOP

RUN

STOP

DNP3/IEC server

RUNNING

RUNNING

RUNNING (synchronization from primary)

RUNNING (synchronization from primary)

Event routing

RUNNING

RUNNING

RUNNING (synchronization from primary)

RUNNING (synchronization from primary)

DNP3/IEC client

RUNNING

RUNNING

STOPPED

STOPPED

SNTP client

RUNNING

RUNNING

RUNNING

RUNNING

Modbus TCP client

RUNNING

RUNNING

STOPPED

STOPPED

Syslog

RUNNING

RUNNING

RUNNING

RUNNING

Modbus TCP server

RUNNING

RUNNING

RUNNING

RUNNING

Firmware upgrade

RUNNING

RUNNING

RUNNING

RUNNING

SNMPv1

RUNNING

RUNNING

RUNNING

RUNNING

SNMPv3

Web server (cyber security setting + diagnostic)

RUNNING

RUNNING

RUNNING

RUNNING

OEB (FDR+LLDP)

RUNNING

RUNNING

RUNNING

RUNNING

Data logging

RUNNING

RUNNING

RUNNING

RUNNING