Introduction
This topic describes the use of the BMENOR2200H module in a standalone M580 system.
Connection Media
Make connections to the BMENOR2200H module with a cable:
upstream connection: Connect the module to a SCADA system through theDNP3, IEC60870-5-101, or IEC60870-5-104 protocols. (A Modbus TCP connection is another option.)
downstream connection: Connect the module to remote server devices and stations through the DNP3, IEC60870-5-101, or IEC60870-5-104 protocols.
Ethernet Connections
There is no Ethernet port on the front of the BMENOR2200H module. The connection to an Ethernet cable is therefore through another Ethernet communications interface module when the Ethernet port on the backplane is enabled:
flat networks: For these networks, we recommend that Ethernet network connections to the BMENOR2200H are through the M580 service port on a BMENOC0301/11 or BMENOS0300 module.
isolated networks: For these networks, we recommend that Ethernet network connections are achieved through a BMENOC0321 module with the IP forwarding function. The installation of multiple BMENOC0321 modules requires the use of a static routing table for the upstream system.