Introduction

You can use the Configuration Management web page to export the cyber security settings for a BMENOR2200H module to import that configuration into another module.
NOTE: Only a security administrator with SECADM credentials can perform these configuration management tasks.

Access the Page

Access the Configuration Management web page through the SETUP tab for the BMENOR2200H module ( SETUP > MENU > MANAGEMENT > Configuration Management ).

Export the Configuration

Export the cyber security configuration file with the EXPORT CONFIGURATION parameters on the Configuration Management tab. The applied settings immediately overwrite the existing settings.

Configure these parameters for the export action:

Parameter

Description

Password

Enter your Password, which is an encryption key to archive the exported configuration file.
NOTE: This same password is used to archive an imported configuration file.

Confirm Password

Re-enter your password.

Export

Click this button to exmport the configuration.

Import the Configuration

Import the cyber security management configuration and apply it to the module with the IMPORT CONFIGURATION parameters on the Configuration Management tab.

Configure these parameters for the import action:

Parameter

Description

Configuration Archive

Select the configuration file you want to import and follow the prompt(s) to confirm your selection.
NOTE: You can use the Browse button to navigate to the appropriate file.

Password

Enter the configuration file password that was assigned to the file when the file was exported.

Save

Check this box to automatically apply the imported configuration immediately after it is uploaded.

Import

Click this button to import the configuration.

Reset the Configuration

Click the Reset button in the RESET CONFIGURATION field to restore the factory default cyber security settings for the module.
NOTE: Restart the module to implement the reset action.

Execute Changes

After you configure any of these parameters, press the Apply button in the page banner to implement your changes.
NOTE: The Apply and Discard buttons are disabled (grayed out) when the configuration is not valid.