Setting
|
Description
|
---|---|
Identification area:
|
|
Buffered
|
Do one of the following:
This check box is de-selected by default.
|
ReportCB Name
|
Enter a 10-character maximum report control name.
|
Description
|
The editable description of the report control block, from 0...50 characters long.
|
Data Set
|
Select the data set to include in the report control block.
|
Report ID
|
A string value, 0...129 characters long, used as the source identifier in report control block transmissions.
|
Conf Rev
|
The read-only revision number for the report control block. The initial value is 10000.
NOTE: This setting is increased in increments of 10000 each time one of the following changes occurs:
|
Parameters area:
|
|
Buffer Time (ms)
|
The time interval in milliseconds for the buffering of internal notifications caused by data-change (dchg) or quality-change (qchg) by the BRCB for inclusion into a single report.
|
Integrity Period
|
Enter a value, in milliseconds, to periodically force the transmission of all values in the data set. Using this setting synchronizes data values in all clients that receive the transmission.
|
Indexed
|
Do one of the following:
This check box is selected by default.
NOTE: The module supports up to 8 instances of indexed report control blocks. |
Index Number
|
Select an index number for the report control block.
|
Trigger Conditions area:
|
|
Data Change
|
Select this check box to transmit a report upon a change in value for an item in the data set.
|
Quality Change
|
Select this check box to transmit a report upon a change in quality for any item in the data set.
|
Period
|
Select this check box to transmit a report of all data set values upon expiration of the Integrity Period.
NOTE: The integrity report is not available in a standby BMENOP0300 module in a redundant M580 network. |
General Interrogation
|
Select this check box to transmit a report, in response to a request from a client, containing values for all data items in the data set.
NOTE:
|
Report Content area:
|
|
Sequence Number
|
Select this check box to include an auto-generated transmission sequence number to the report control block transmission. This lets the client determine if all transmissions have been received.
|
Report Timestamp
|
Select this check box to include a time stamp in the report control block transmission.
|
Reason for inclusion
|
The reason for sending this report, for example:
|
Data Set Name
|
Select this check box to include the configured data set name in the report control block transmission.
|
Data Reference
|
The name of the data set referenced in the report.
|
Buffer Overflow
|
Select this check box to include the buffer overflow in the report content.
This check box is de-selected by default.
|
Entry Id
|
Select this check box to include the entry ID in the report content.
This check box is de-selected by default.
|
Configuration Revision
|
Select this check box to include the Configuration Revision setting of the report control block in the transmission.
|
Step
|
Action
|
---|---|
1
|
In the Report Control list, click the + button.
Result: A new report control block appears in list, with the default name report_n (where n represents the sequential number of the control block).
|
2
|
Enter values for the Identification, Parameters, Trigger Conditions and Report Content settings. Refer to the description of Report Control Settings (above).
NOTE: To enter a setting value, click Enter or move your cursor and click outside the setting input field. |
3
|
Save your edits.
|
Step
|
Action
|
---|---|
1
|
In the Report Control list, select an existing control block.
Result: The settings for the selected report control block appear in the Identification, Parameters, Trigger Conditions and Report Content areas.
|
2
|
Enter values for the Identification, Parameters, Trigger Conditions and Report Content settings. Refer to the section Report Control Settings (above).
NOTE: To enter a setting value, click Enter or move your cursor and click outside the setting input field. |
3
|
Save your edits.
|
Step
|
Action
|
---|---|
1
|
In the Report Control list, select an existing control block.
Result: The settings for the selected report control block appear in the Identification, Parameters, Trigger Conditions and Report Content areas.
|
2
|
Click the – button.
Result: The control block is removed from the list.
|
3
|
Save your edits.
|