Uploading and Downloading Configuration Settings
Original instructions
Introduction
When you finish entering configuration settings for the BMENOP0300 module, perform the following tasks:
After the built application is transferred to the CPU, the CPU transfers configuration settings to the BMENOP0300 module.
NOTE: Configuration settings do not take effect until they are successfully downloaded from your PC to the CPU and from the CPU to the BMENOP0300 module.
Updating the Configuration
After you input configuration settings for the BMENOP0300 module, update the configuration as follows:
Step
Action
1
Close the Modicon IEC 61850 Configuration Tool.
Result: The Confirm dialog opens.
2
Click Yes to save your edits.
Result: The Confirm dialog closes. In the Configuration tab of the BMENOP0300 module Properties window, the Update application button is enabled.
3
Click the Update application button.
Clicking Update application button creates variables that display the following information and commands for your Control Expert project:
Compiling the Project
To compile the updated project, in Control Expert select either Build → Build Changes or Build → Rebuild All Project. Check the Output window to confirm the process succeeded.
Downloading the Application Program
After the application has been compiled, connect Control Expert to the CPU (PLC → Connect), then download the application to the CPU (PLC → Transfer Project to PLC).
To transfer the compiled application program from Control Expert to the CPU, follow these steps:
Step
Action
1
Connect Control Expert to the CPU: Select PLC → Connect.
2
Stop CPU operations if the CPU is executing an earlier version of the application: Select PLC → Stop.
3
Download the application to the CPU: Select (PLC → Transfer Project to PLC.
On next power-up, the BMENOP0300 module compares the configuration in the CPU against the one stored in the module.
Uploading the Application Program
To transfer the current application program from the CPU to Control Expert, follow these steps:
Step
Action
1
Connect Control Expert to the CPU: Select PLC → Connect.
2
Stop CPU operations if the CPU is executing an earlier version of the application: Select PLC → Stop.
3
Upload the application to the CPU: Select (PLC → Transfer Project from PLC.
NOTE: Uploading the application program does not also upload the IEC 61850 settings of the BMENOP0300 module. To apply IEC 61850 settings, confirm that you have saved these settings in a .prj file during a previous configuration. For instructions on how to apply saved IEC 61850 settings, refer to the topic Selecting the IEC 61850 Edition.
Archiving the Application Program
To archive the application in Control Expert, do one of the following:
NOTE: Saving your application as an .STA or .STU file type saves the entire Control Expert project, including the IEC 61850 project file. If you export the application as a .ZEF file type, the IEC 61850 project file is not saved.