Step
|
Action
|
---|---|
1
|
In the DTM Browser, find the name that is assigned to your Ethernet communications module.
|
2
|
Right-click on the module name.
|
3
|
Scroll to Device menu → Diagnosis.
|
4
|
In the left pane of the Diagnosis window, select the communication module node.
|
5
|
Select the Bandwidth tab to open that page.
|
Checkbox
|
Description
|
---|---|
Selected
|
|
De-selected
|
|
Parameter
|
Description
|
---|---|
I/O - Scanner:
|
|
EtherNet/IP Sent
|
The number of EtherNet/IP packets the module has sent in packets/second.
|
EtherNet/IP Received
|
The number of EtherNet/IP packets the module has received in packets/second.
|
Modbus TCP Received
|
The number of Modbus TCP requests the module has sent in packets/second.
|
Modbus TCP Responses
|
The number of Modbus TCP responses the module has received in packets/second.
|
I/O - Adapter:
|
|
EtherNet/IP Sent
|
The number of EtherNet/IP packets (per second) the module has sent in the role of a local slave.
|
EtherNet/IP Received
|
The number of EtherNet/IP packets (per second) the module has received in the role of a local slave.
|
I/O - Module
|
|
Module Capacity
|
The maximum number of packets (per second) that the module can process.
|
Module Utilization
|
The percentage of communication module capacity being used by the application.
|
Messaging - Client:
|
|
EtherNet/IP Activity
|
The number of explicit messages (packets per second) sent by the module using the EtherNet/IP protocol.
|
Modbus TCP Activity
|
The number of explicit messages (packets per second) sent by the module using the Modbus TCP protocol.
|
Messaging - Server:
|
|
EtherNet/IP Activity
|
The number of server messages (packets per second) received by the module using the EtherNet/IP protocol.
|
Modbus TCP Activity
|
The number of server messages (packets per second) received by the module using the Modbus TCP protocol.
|
Module:
|
|
Processor Utilization
|
The percent of Ethernet communication module processor capacity used by the present level of communication activity.
|