Introducing Diagnostics in the Control Expert DTM
Original instructions
Introduction
The Control Expert DTM provides diagnostics information that is collected at configured polling intervals. Use this information to diagnose the operation of your Ethernet communications module.
Connect the DTM
Before you can open the diagnostics page, make the connection between the DTM for the target communication module:
Step
Action
1
Open a Control Expert project that includes the Ethernet communications module.
2
Open the Control Expert DTM Browser (Tools → DTM Browser).
3
Find the name that is assigned to your Ethernet communications module in the DTM Browser.
4
Right-click on the module name.
5
Scroll to Connect.
Open the Page
Access the Diagnosis information:
Step
Action
1
Right-click the name that is assigned to your Ethernet communications module in the DTM Browser.
2
Scroll to Device Menu → Diagnosis to view the available diagnostics pages.
Diagnostics Information
The diagnostics window has two distinct areas:
When the appropriate DTM is connected to the physical communication module, Control Expert sends an explicit message request once per second to detect the state of the communication module and of all the remote devices and EtherNet/IP connections linked to that module.
Control Expert places one of these status icons over the module, device, or connection in the left pane of the Diagnostic window to indicate its current status:
Icon
Communication module
Connection to a remote device
Run state is indicated.
The health bit for every EtherNet/IP connection and Modbus TCP request (to a remote device, sub-device, or module) is set to active (1).
One of these states is indicated:
  • unknown
  • stopped
  • not connected
The health bit for at least one EtherNet/IP connection or Modbus TCP request (to a remote device, sub-device, or module) is set to inactive (0).