Step
|
Action
|
---|---|
1
|
Open a Control Expert project that includes a BMENOC0301/11 module.
|
2
|
Open the DTM Browser (Tools → DTM Browser).
|
3
|
In the DTM Browser, find the name that you assigned to the BMENOC0301/11 module..
|
4
|
Double-click the name of the BMENOC0301/11 to open the configuration window.
NOTE: You can also right-click on the module and scroll to Open to open the configuration window. |
5
|
Select Services in the navigation tree.
|
6
|
Enable or disable each feature:
|
7
|
Click a button:
|
8
|
Expand (+) Services in the navigation tree to view the enabled services.
|
Service
|
Description
|
Default
|
---|---|---|
NOTE: The SNMP service is enabled by default and cannot be disabled. |
enabled
|
|
Provide IP addressing parameters and operating parameters to other Ethernet devices.
|
enabled
|
|
Employ RSTP in combination with other similarly-configured network devices to manage redundant physical connections and create a loop-free logical path that connects network devices.
|
enabled
|
|
Provide the source time synchronization signal for the PLC controller, which manages an internal clock to maintain this time.
|
disabled
|
|
Add DSCP tags to Ethernet packets so that network switches can prioritize the transmission and forwarding of Ethernet packets.
NOTE: Before enabling QoS tagging, confirm that devices connected to the Ethernet communication module support QoS tagging. |
enabled
|
|
The system allows connection to a control network through the service port.
|
enabled
|