 Step     
 | 
 Action     
 | 
|---|---|
| 
 1     
 | 
 Find the Ethernet communication module in the Control Expert DTM Browser.     
 | 
| 
 2      
 | 
 Right-click the module and scroll to Device menu → Additional functions → Advanced Mode.      
 | 
| 
 3      
 | 
 Double-click the module in the DTM Browser to view the Channel Properties.      
 | 
| 
 4      
 | 
 Expand (+) Channel Properties.      
 | 
| 
 5       
 | 
 Select EtherNet/IP to view the items in the Group/Parameter column:       
  | 
| 
 Parameter        
 | 
 Value        
 | 
 Comment        
 | 
|---|---|---|
| 
 FW_Open I/O Connection Timeout (msec)        
 | 
 4960         
 | 
 Specifies the amount of time the scanner waits for FW_Open response of an I/O connection.         
 | 
| 
 FW_Open EM Connection Timeout (msec)         
 | 
 3000         
 | 
 Specifies the amount of time the scanner waits for FW_Open response of an EM connection.         
 | 
| 
 EM Connection RPI (msec)         
 | 
 10000         
 | 
 Sets T->O and O->T RPI for all EM (explicit messaging) connections.          
 | 
| 
 EM Request Timeout (sec)          
 | 
 10          
 | 
 Specifies the amount of time the scanner will wait between the request and the response of an explicit message.          
 | 
| 
 Parameter           
 | 
 Value           
 | 
 Comment           
 | 
|---|---|---|
| 
 Allow RESET via explicit message           
 | 
 False            
 | 
 (Default.) The scanner ignores the Identity object reset service request.            
 | 
| 
 True            
 | 
 The scanner will reset if an Identity object reset service request is received.            
 | 
|
| 
 Behavior when CPU state is STOP            
 | 
 Idle            
 | 
 (Default.) The EtherNet/IP I/O connection stays open, but the Run/Idle flag is set to Idle.             
 | 
| 
 Stop             
 | 
 The EtherNet/IP IO connection is closed.             
 |