Firmware Update with Unity Loader
Original instructions
Introduction
You can update the firmware on the Ethernet communications module by downloading a new firmware version with Unity Loader.
The firmware download can be performed by connecting to the Ethernet network through ETH 1.
Refer to Unity Loader, User Guide for a description of the download procedure.
Enabling the Update
To enable the firmware update, check the security settings.
Firmware File
The firmware file is a *.ldx file.
Procedure
Update the firmware for the Ethernet communications module and the BMEXBP••00 rack:
Step
Action
1
Install Unity Loader software.
2
Connect the PC that is running Unity Loader to the Ethernet communications module.
3
Launch Unity Loader.
4
Click Firmware tab.
5
In the PC list box, select the .ldx file that contains the firmware file.
6
When connected with Ethernet, check that the MAC address indicated in the PLC box corresponds to the MAC address marked on the connected device (PLC or Ethernet communication module).
7
Check that transfer sign is green to allow transfer from PC to connected device.
8
Click Transfer.
9
Click Close.